Miniature Circuit Breakers (MCBs) are compact electro-mechanical devices for up to 63A, for protection against overload and short-circuit conditions.
Mainly used for household applications and similar.
Standard: IEC60898-1
Breaking capacity:
4.5kA to 10kA 230/400VAC,
10kA 250VDC.
Product Specification:
Miniature circuit breakers (MCB)
Type |
BHW-T10 |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Miniature circuit breakers (MCB) |
|||||||||||
No. of poles P |
1 |
2 |
3 |
4 |
1 |
2 |
3 |
4 |
|||
Instantaneous tripping |
Type B |
Type C, D 1 |
|||||||||
Rated insulation voltage U i [V] |
660 |
660 |
|||||||||
Rated c urrent I n [A] at ambient temperature 30° C |
6, 10, 16, 20, 25, 32, 40, 50, 63 |
0.5, 1, 2, 3, 4, 5, 6, 10, 16, 20, 25, 32, 40, 50, 62 |
|||||||||
Rated short-circuit capacity [kA] |
IEC/EN 60898-1 (Icn) |
AC |
240 V |
10 |
10 |
||||||
240 V/ 415 V |
10 |
10 |
|||||||||
415 V |
— |
10 |
— |
10 |
|||||||
Energy limiting class 2 |
|
||||||||||
Number of operating cycles |
Without current |
|
|||||||||
With current |
|
||||||||||
Type of overcurrent release |
Thermal-magnetic |
||||||||||
Mounting |
IEC 35 mm rail |
||||||||||
Applicable wire size |
1 to 25 mm² |
||||||||||
Mass [kg] |
0.13 |
0.26 |
0.39 |
0.52 |
0.13 |
0.26 |
0.39 |
0.52 |
|||
Accessories (optional) 3 |
Auxiliary switch (AX) |
o |
|||||||||
Terminal connection |
Solderless |
||||||||||
Based on Standard |
IEC/EN 60898-1 |
||||||||||
CE marking |
o |
Type C: (5 In <, 10 In), Type D: (10 In <, 20 In)
Except for type D
Available soon
Standard: IEC61008
Type of residual current: Type AC
Product Specification:
Residual current breakers (RCCB) |
|||
---|---|---|---|
Type |
BVW-T |
||
No. of poles P |
2 (1+N) 1 |
4 (3+N) 1 |
|
Rated c urrent I n [A] at ambient temperature 30° C |
25, 40, 63 |
||
Rated voltage [V AC] |
240 |
415 |
|
Rated current sensitivity I g n [mA] |
30, 300 |
||
Max. operating time at I g n [s] |
0.04 |
||
Pulsating current sensitivity |
Type AC |
||
Rated making and breaking capacity I m [A] |
500 (In 25, 40 A), 630 (In 63 A) |
||
Rated conditional short-circuit current I nc [kA] |
5 |
||
Rated residual making and breaking capacity I g m [A] |
500 (In 25, 40 A), 630 (In 63 A) |
||
Rated conditional residual short-circuit current I g C [kA] |
6 |
||
Number of o perating cycles |
Without current |
4,000 2 |
|
With current |
2,000 |
||
Type of overcurrent release |
— |
||
Mounting |
IEC 35 mm rail |
||
Applicable wire size |
1 to 25 mm² |
||
Mass [kg] |
0.22 |
0.44 |
|
Terminal connection |
Solderless |
||
Based on standard |
IEC/EN 61008-1 |
||
CE marking |
o |
1 N pole is a switched neutral pole (without overcurrent release device).
Standard: IEC61009
Breaking capacity:
4.5kA 230VAC
Type of residual current: Type AC
Product Specification:
Type |
BV-DN |
NV125-CV |
NV250-CV |
||
---|---|---|---|---|---|
Rated current I n [A] |
|
10, 16, 20, 25, 32, 40 |
80, 100, 125 |
150, 175, 200, 225, 250 |
|
Number of poles |
|
2 (1+N) |
3 |
3 |
|
Rated voltage [V AC] |
|
230 |
100–440 |
100–440 |
|
Rated current sensitivity [mA] |
|
30 |
100/200/500 selectable |
100/200/500 selectable |
|
Max. operating time [s] |
|
0.04 |
0.45/1.0/2.0 selectable |
0.45/1.0/2.0 selectable |
|
Pulsating current sensitivity |
|
AC |
A (Harmonic Surge Ready) |
A (Harmonic Surge Ready) |
|
Rated breaking capacity [kA] |
230 V AC |
4.5 |
30 |
36 |
|
440 V AC |
— |
10 |
15 |
||
Number of operating cycles |
Without current |
20000 |
10000 |
8000 |
|
With current |
20000 (In 10, 16,20 A) 15000 (In 25 A) 10000 (In 32, 40 A) |
6000 |
4000 |
||
Dimensions [mm] |
a |
36 |
90 |
105 |
|
b |
88 |
130 |
165 |
||
c |
44 |
68 |
68 |
||
ca |
70 |
90 |
92 |
||
Mass [kg] |
0.19 |
1 |
1.7 |
||
Automatic tripping device |
Thermal-magnetic |
Thermal-magnetic |
Thermal-magnetic |
||
Based on standard |
IEC61009-1 |
IEC60947-2 |
IEC60947-2 |
||
Breaker type |
MCB |
MCCB |
MCCB |
||
CE marking |
Self-declaration |
Self-declaration |
TÜV approval |
Type |
2P (1P+N) |
3P |
---|---|---|
RCBO (Residual current circuit breakers with overcurrent protection) |
||
BV-DN 1PN 10A 30MA N |
248280 |
— |
BV-DN 1PN 16A 30MA N |
248283 |
— |
BV-DN 1PN 20A 30MA N |
248286 |
— |
BV-DN 1PN 25A 30MA N |
248289 |
— |
BV-DN 1PN 32A 30MA N |
248292 |
— |
BV-DN 1PN 10A 40MA N |
248295 |
— |
ELCB (Earth leakage circuit breakers) |
||
NV125-CV 3P 80A 2-440V 1.2.500MA JIEN CE |
— |
265624 |
NV125-CV 3P 100A 2-440V 1.2.500MA JIEN CE |
— |
265625 |
NV125-CV 3P 125A 2-440V 1.2.500MA JIEN CE |
— |
265626 |
NV250-CV 3P 150A 2-440V 1.2.500MA JIEN CE |
— |
265792 |
NV250-CV 3P 175A 2-440V 1.2.500MA JIEN CE |
— |
265793 |
NV250-CV 3P 200A 2-440V 1.2.500MA JIEN CE |
— |
265794 |
NV250-CV 3P 225A 2-440V 1.2.500MA JIEN CE |
— |
265795 |
NV250-CV 3P 250A 2-440V 1.2.500MA JIEN CE |
— |
265796 |