Mitsubishi low voltage circuit breakers prolong the lifespan of electrical equipment.
For over a half of a century Mitsubishi low voltage circuit breakers meet the needs of market. Including the WS-V series equipped with a new breaking technology, Mitsubishi Low Voltage Circuit Breakers have various lineups depending on the electric power market and the machinery.
Make electrical equipment multi-functional by means of Mitsubishi air circuit breakers that are suitable for protection of the main circuit.
Air circuit breakers have many advantages, among them adding higher reliability during switching. They can be used to extend the area of selective coordination trough expansion of the rated short-time withstand current, for use in main circuit ports.
This kind of breaker is used as the main power breaker of the supply such as buildings, factories and ships etc. and satisfy the various needs.
SUPER AE – WORLD SUPER SERIES |
AE1000-SW |
AE1250-SW |
AE1600-SW |
AE2000-SWA |
||||
---|---|---|---|---|---|---|---|---|
Frame size |
A |
1000 |
1250 |
1600 |
2000 |
|||
Rated insulation voltage (AC V) 50/60 Hz |
U i |
1000 |
||||||
Rated operating voltage (AC V) 50/60 Hz |
U e |
690 |
||||||
Rated impulse withstand voltage (kV) |
U imp |
12 |
||||||
Pollution degree |
3 |
|||||||
Number of poles |
P |
3 / 4 |
3 / 4 |
3 / 4 |
3 / 4 |
|||
Rated curren t I n (CT rating) |
1000 |
1250 |
1600 |
2000 |
||||
Adjustment range Rated current I r (A) |
General use (current rating adjustable 0.5 to 1.0 x I n 0.05 step) |
500-550-600-650- 700-750-800-850- 900-950 -1000 |
625-687.5-750-812.5- 875-937.5-1000-1062.5-1125-1187.5-1250 |
800-880-960-1040- 1120-1200-1280-1360- 1440-1520-1600 |
1000-1100-1200-1300- 1400-1500-1600-1700- 1800-1900-2000 |
|||
Generator protection(current rating fixed) |
400 ≤ I r ≤ 1000 |
800 ≤ I r ≤ 1250 |
1000 ≤ I r ≤ 1600 |
1250 ≤ I r ≤ 2000 |
||||
Rated current of neutral pole |
A |
1000 |
1250 |
1600 |
2000 |
|||
IEC 60947-2, EN 60947-2, VDE, JIS C 8201-2-1 |
Ultimate breaking capacity I cu (kA rms) |
690 V AC |
65 |
65 |
65 |
65 |
||
600 V AC |
65 |
65 |
65 |
65 |
||||
240–500 V AC |
65 |
65 |
65 |
65 |
||||
With MCR |
690 V AC |
65 |
65 |
65 |
65 |
|||
600 V AC |
65 |
65 |
65 |
65 |
||||
240–500 V AC |
65 |
65 |
65 |
65 |
||||
Withoutinstantaneous |
690 V AC |
25 a |
25 a |
25 a |
25 a |
|||
500 V AC |
25 a |
25 a |
25 a |
25 a |
||||
Rated service breaking capacity Ics (kA rms) % lcu |
||||||||
Rated making capacity I cm (kA, peak) |
690 V AC |
143 |
143 |
143 |
143 |
|||
600 V AC |
143 |
143 |
143 |
143 |
||||
240–500 V AC |
143 |
143 |
143 |
143 |
||||
With MCR |
690 V AC |
143 |
143 |
143 |
143 |
|||
600 V AC |
143 |
143 |
143 |
143 |
||||
240–500 V AC |
143 |
143 |
143 |
143 |
||||
Withoutinstantaneous |
690 V AC |
52.5 |
52.5 |
52.5 |
52.5 |
|||
500 V AC |
52.5 |
52.5 |
52.5 |
52.5 |
||||
Disconnector: switching capacity (6x I r at 690V AC) |
O |
O |
O |
O |
||||
Rated short time withstand current (kA rms) I cw |
1 s |
65 |
65 |
65 |
65 |
|||
2 s |
60 |
60 |
60 |
60 |
||||
3 s |
50 |
50 |
50 |
50 |
||||
Maximum total breaking time |
ms |
40 f |
40 f |
40 f |
40 f |
|||
Closing time |
ms |
80 |
80 |
80 |
80 |
|||
Number of operating cycles (ON/OFF) b |
With ratedcurrent |
500 V AC I n |
5000 |
5000 |
5000 |
1500 |
||
690 V AC I n |
5000 |
5000 |
5000 |
1500 |
||||
Without rated current d |
25000 |
25000 |
25000 |
25000 |
||||
Connecting terminal |
Horizontal terminal |
O |
O |
O |
— |
|||
Vertical terminal |
O |
O |
O |
O c |
||||
Front terminal |
O |
O |
O |
— |
||||
Dimensions (HxWxD) mm |
Fixed type |
3-pole |
410x340x290 |
|||||
4-pole |
410x425x290 |
|||||||
Drawout type |
3-pole |
430x300x368 |
||||||
4-pole |
430x385x368 |
|||||||
Weight kg |
Fixed type |
3-pole |
41 |
41 |
42 |
47 |
||
4-pole |
51 |
51 |
52 |
57 |
||||
Drawout type(with cradle) |
3-pole |
64 |
64 |
65 |
70 |
|||
4-pole |
78 |
78 |
79 |
84 |
||||
Cradle only |
3-pole |
26 |
26 |
26 |
31 |
|||
4-pole |
30 |
30 |
30 |
35 |
SUPER AE – WORLD SUPER SERIES |
AE2000-SW |
AE2500-SW |
AE3200-SW |
AE4000-SWA |
AE4000-SW |
AE5000-SW |
AE6300-SW |
||||
---|---|---|---|---|---|---|---|---|---|---|---|
Frame size |
A |
2000 |
2500 |
3200 |
4000 |
4000 |
5000 |
6300 |
|||
Rated insulation voltage (AC V) 50/60 Hz |
U i |
1000 |
1000 |
||||||||
Rated operating voltage (AC V) 50/60 Hz |
U e |
690 |
690 |
||||||||
Rated impulse withstand voltage (kV) |
Uimp |
12 |
12 |
||||||||
Pollution degree |
3 |
3 |
|||||||||
Number of poles |
P |
3 / 4 |
3 / 4 |
3 / 4 |
3 / 4 |
3 / 4(HN, FN) g |
3 / 4(HN, FN) g |
3 / 4(HN, FN) g |
|||
Rated curren t I n (CT rating) |
2000 |
2500 |
3200 |
4000 |
4000 |
5000 |
6300 |
||||
Adjustment range Rated current I r (A) |
General use (current rating adjustable 0.5 to 1.0 x I n 0.05 step) |
1000-1100-1200-1300- 1400-1500-1600-1700- 1800-1900-2000 e |
1250-1375-1500-1625- 1750-1875-2000-2125- 2250-2375-2500 |
1600-1760-1920-2080- 2240-2400-2560-2720- 2880-3040-3200 |
2000-2200-2400-2600- 2800-3000-3200-3400- 3600-3800-4000 |
2000-2200-2400-2600- 2800-3000-3200-3400- 3600-3800-4000 |
2500-2750-3000-3250- 3500-3750-4000-4250- 4500-4750-5000 |
3150-3465-3780-4095- 4410-4725-5040-5355- 5670-5985-6300 |
|||
Generator protection(current rating fixed) |
800 ≤ I r ≤ 2000 |
1600 ≤ I r ≤ 2500 |
2000 ≤ I r ≤ 3200 |
2500 ≤ I r ≤ 4000 |
2500 ≤ I r ≤ 4000 |
3150 ≤ I r ≤ 5000 |
4000 ≤ I r ≤ 6300 |
||||
Rated current of neutral pole |
A |
2000 |
2500 |
3200 |
4000 |
2000 (4000) h |
2500 (5000) h |
3150 (6300) h |
|||
IEC 60947-2,EN 60947-2,VDE, JIS C 8201-2-1 |
Ultimate breaking capacity Icu (kA rms) |
690 V AC |
75 |
75 |
75 |
75 |
85 |
85 |
85 |
||
600 V AC |
75 |
75 |
75 |
75 |
85 |
85 |
85 |
||||
240–500 V AC |
85 |
85 |
85 |
85 |
130 |
130 |
130 |
||||
With MCR |
690 V AC |
75 |
75 |
75 |
75 |
85 |
85 |
85 |
|||
600 V AC |
75 |
75 |
75 |
75 |
85 |
85 |
85 |
||||
240–500 V AC |
75 |
75 |
75 |
75 |
100 |
100 |
100 |
||||
Withoutinstantaneous |
690 V AC |
45 a |
45 a |
45 a |
45 a |
65 a |
65 a |
65 a |
|||
500 V AC |
45 a |
45 a |
45 a |
45 a |
65 a |
65 a |
65 a |
||||
Rated service breaking capacity Ics (kA rms) % l cu |
100 % |
100 % |
|||||||||
Rated making capacity Icm (kA, peak) |
690 V AC |
165 |
165 |
165 |
165 |
187 |
187 |
187 |
|||
600 V AC |
165 |
165 |
165 |
165 |
187 |
187 |
187 |
||||
240–500 V AC |
187 |
187 |
187 |
187 |
286 |
286 |
286 |
||||
With MCR |
690 V AC |
165 |
165 |
165 |
165 |
187 |
187 |
187 |
|||
600 V AC |
165 |
165 |
165 |
165 |
187 |
187 |
187 |
||||
240–500 V AC |
165 |
165 |
165 |
165 |
220 |
220 |
220 |
||||
Withoutinstantaneous |
690 V AC |
94.5 |
94.5 |
94.5 |
94.5 |
143 |
143 |
143 |
|||
500 V AC |
94.5 |
94.5 |
94.5 |
94.5 |
143 |
143 |
143 |
||||
Disconnector: switching capacity (6x I r at 690V AC) |
O |
O |
O |
O |
O |
O |
O |
||||
Rated short time withstand current (kA rms) I cw |
1 s |
75 |
75 |
75 |
75 |
100 |
100 |
100 |
|||
2 s |
75 |
75 |
75 |
75 |
85 |
85 |
85 |
||||
3 s |
65 |
65 |
65 |
65 |
85 |
85 |
85 |
||||
Maximum total breaking time |
ms |
40 f |
40 f |
40 f |
40 f |
50 f |
50 f |
50 f |
|||
Closing time |
ms |
80 |
80 |
80 |
80 |
80 |
80 |
80 |
|||
Number of operating cycles(ON/OFF) b |
With ratedcurrent |
500 V AC In |
1500 |
1500 |
1000 |
500 |
1000 |
1000 |
1000 |
||
690 V AC In |
1500 |
1500 |
1000 |
500 |
1000 |
1000 |
1000 |
||||
Without rated current d |
20000 |
20000 |
20000 |
20000 |
10000 (3P)/5000 (4P) |
10000 (3P)/5000 (4P) |
10000 (3P)/5000 (4P) |
||||
Connecting terminal |
Horizontal terminal |
O |
O |
O |
— |
— |
— |
— |
|||
Vertical terminal |
O |
O |
O |
O c |
O c |
O c |
O c |
||||
Front terminal |
O |
O |
O |
— |
— |
— |
— |
||||
Dimensions (HxWxD) mm |
Fixed type |
3-pole |
410x475x290 |
414x873x290 |
|||||||
4-pole |
410x605x290 |
414x1003 (1133)x290 h |
|||||||||
Drawout type |
3-pole |
430x435x368 |
430x439x368 |
480x875x368 |
|||||||
4-pole |
430x565x368 |
430x569x368 |
480x1005 (1135)x368 h |
||||||||
Weight kg |
Fixed type |
3-pole |
60 |
61 |
63 |
81 |
160 |
160 |
160 |
||
4-pole |
72 |
73 |
75 |
99 |
180 (200) h |
180 (200) h |
180 (200) h |
||||
Drawout type(with cradle) |
3-pole |
92 |
93 |
95 |
108 |
233 |
233 |
240 |
|||
4-pole |
113 |
114 |
116 |
136 |
256 (279) h |
256 (279) h |
263 (286) h |
||||
Cradle only |
3-pole |
35 |
35 |
35 |
49 |
118 |
118 |
125 |
|||
4-pole |
43 |
43 |
43 |
61 |
133 (148) h |
133 (148) h |
140 (155) h |
Wide assortment of products that is highly suitable for protection against overload and short-circuit conditions.
These are basic products for the protection of low voltage circuits. The WS-V series, Mitsubishi's latest series of Low Voltage Circuit Breakers, offers a number of different versions, including "F-style" small size breakers, with improved usability.
The molded case circuit breaker (MCCB) opens and closes a low voltage circuit, and breaks the fault current (an overload current or short circuit current) automatically, to protect the wirings/conductors of the circuit.
Type/series |
WS-V series |
|||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
NF32-SV |
NF63-SV |
NF125-SV |
NF125-SGV |
NF125-SEV |
NF160-SGV |
NF250-SV |
NF250-SGV |
NF250-SEV |
||||||
S series |
Rated current I n max. [A] |
32 |
63 |
125 |
125* |
125* |
160* |
250 |
250* |
250* |
||||
Rated insulation voltage U i [V] |
AC |
600 |
600 |
690 |
690 |
690 |
690 |
690 |
690 |
690 |
||||
Number of poles |
3 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
|||||
Ratedbreakingcapacity[kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2VDE 0660 |
AC a (50/60 Hz) |
690 V |
— |
— |
8/8 |
8/8 |
8/8 |
8/8 |
8/8 |
8/8 |
8/8 |
||
500 V |
2.5/2.5 |
7.5/7.5 |
18/18 |
30/30 |
30/30 |
30/30 |
30/30 |
30/30 |
30/30 |
|||||
440 V |
2.5/2.5 |
7.5/7.5 |
25/25 |
36/36 |
36/36 |
36/36 |
36/36 |
36/36 |
36/36 |
|||||
400 V |
5/5 |
7.5/7.5 |
30/30 |
36/36 |
36/36 |
36/36 |
36/36 |
36/36 |
36/36 |
|||||
230 V |
7.5/7.5 |
15/15 |
30/30 |
85/85 |
85/85 |
85/85 |
85/85 |
85/85 |
85/85 |
|||||
Dimensions WxHxD |
[mm] |
75x130x68 |
75/100x130x68 |
90/120/x130x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
||||
Type |
NF125-LGV |
NF160-LGV |
NF250-LGV |
|||||||||||
L series |
Rated current I n max. [A] |
125* |
160* |
250* |
||||||||||
Rated insulation voltage U i [V] |
AC |
690 |
690 |
690 |
||||||||||
Number of poles |
3/4 |
3/4 |
3/4 |
|||||||||||
Ratedbreakingcapacity[kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2VDE 0660 |
AC a (50/60 Hz) |
690 V |
8/8 |
8/8 |
8/8 |
||||||||
500 V |
36/36 |
36/36 |
36/36 |
|||||||||||
440 V |
50/50 |
50/50 |
50/50 |
|||||||||||
400 V |
50/50 |
50/50 |
50/50 |
|||||||||||
230 V |
90/90 |
90/90 |
90/90 |
|||||||||||
Dimensions WxHxD |
[mm] |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
||||||||||
Type |
NF63-HV |
NF125-HGV |
NF125-HEV |
NF160-HGV |
NF250-HGV |
NF250-HEV |
||||||||
H series |
Rated current I n max. [A] |
63 |
125* |
125* |
160* |
250* |
250* |
|||||||
Rated insulation voltage U i [V] |
AC |
690 |
690 |
690 |
690 |
690 |
690 |
|||||||
Number of poles |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
||||||||
Ratedbreakingcapacity[kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2VDE 0660 |
AC a (50/60 Hz) |
690 V |
2.5/2.5 |
10/8 |
10/8 |
10/8 |
10/8 |
10/8 |
|||||
500 V |
7.5/7.5 |
50/38 |
50/38 |
50/38 |
50/50 |
50/50 |
||||||||
440 V |
10/8 |
65/65 |
65/65 |
65/65 |
65/65 |
65/65 |
||||||||
400 V |
10/8 |
75/75 |
75/75 |
75/75 |
75/75 |
75/75 |
||||||||
230 V |
25/19 |
100/100 |
100/100 |
100/100 |
100/100 |
100/100 |
||||||||
Dimensions WxHxD |
[mm] |
75/100x130x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
|||||||
Type |
NF125-RGV |
NF250-RGV |
||||||||||||
R series |
Rated current I n max. [A] |
125* |
250* |
|||||||||||
Rated insulation voltage U i [V] |
AC |
690 |
690 |
|||||||||||
Number of poles |
3 |
3 |
||||||||||||
Ratedbreakingcapacity[kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2VDE 0660 |
AC a (50/60 Hz) |
690 V |
— |
— |
|||||||||
500 V |
— |
— |
||||||||||||
440 V |
125/125 |
125/125 |
||||||||||||
400 V |
150/150 |
150/150 |
||||||||||||
230 V |
150/150 |
150/150 |
||||||||||||
Dimensions WxHxD |
[mm] |
105x165x68 |
105x165x68 |
|||||||||||
Type |
NF125-UV |
NF250-UV |
||||||||||||
U series |
Rated current I n max. [A] |
125 |
250 |
|||||||||||
Rated insulation voltage U i [V] |
AC |
690 |
690 |
|||||||||||
Number of poles |
3/4 |
3/4 |
||||||||||||
Ratedbreakingcapacity[kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2VDE 0660 |
AC a (50/60 Hz) |
690 V |
10/10 |
15/15 |
|||||||||
500 V |
200/200 |
200/200 |
||||||||||||
440 V |
200/200 |
200/200 |
||||||||||||
400 V |
200/200 |
200/200 |
||||||||||||
230 V |
200/200 |
200/200 |
||||||||||||
Dimensions WxHxD |
[mm] |
105/140x240x68 |
105/140x240x68 |
|||||||||||
Type |
DSN32-SV |
DSN63-SV |
DSN125-SGV |
DSN160-SGV |
DSN250-SGV |
|||||||||
Disconnectors |
Rated current I n max. [A] |
32 |
63 |
125 |
160 |
250 |
||||||||
Rated insulation voltage U i [V] |
AC/DC |
600 |
600 |
690 |
690 |
690 |
||||||||
Rated voltage U e[V] |
AC (50/60 Hz)/DC |
500/250 |
500/250 |
690/300 |
690/300 |
690/300 |
||||||||
Number of poles |
3 |
3/4 |
3/4 |
3/4 |
3/4 |
|||||||||
Max. switching current [A] (breaking) |
AC/DC |
256/128 |
504/252 |
1000/500 |
1280/640 |
2000/1000 |
||||||||
Dimensions WxHxD |
[mm] |
75x130x68 |
75/120x130x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
a DC on request b In case of solderless terminal, interrupting capacity reduces. * adjustable
Type/series |
WS series |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
NF400-SEW |
NF630-SEW |
NF800-SEW |
NF1000-SEW |
NF1250-SEW |
NF1600-SEW |
||||||
S series |
Rated current I n max. [A] |
400* |
630* |
800* |
1000* |
1250* |
1600* |
||||
Rated insulation voltage U i [V] |
AC |
690 |
690 |
690 |
690 |
690 |
690 |
||||
Number of poles |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
|||||
Rated breakingcapacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
10/10 b |
10/10 |
10/10 |
25/13 |
25/13 |
25/13 |
||
500 V |
30/30 b |
30/30 |
30/30 |
65/33 |
65/33 |
65/33 |
|||||
440 V |
42/42 b |
42/42 |
42/42 |
85/43 |
85/43 |
85/43 |
|||||
400 V |
50/50 b |
50/50 |
50/50 |
85/43 |
85/43 |
85/43 |
|||||
230 V |
85/85 b |
85/85 |
85/85 |
125/63 |
125/63 |
125/63 |
|||||
Dimensions WxHxD |
[mm] |
140/185x257x103 |
140/185x257x103 |
210/280x275x103 |
210/280x406x140 |
210/280x406x140 |
210/280x406x140 |
||||
Type |
NF400-HEW |
NF630-HEW |
NF800-HEW |
||||||||
H series |
Rated current I n max. [A] |
400* |
630* |
800* |
|||||||
Rated insulation voltage U i [V] |
AC |
690 |
690 |
690 |
|||||||
Number of poles |
3/4 |
3/4 |
3/4 |
||||||||
Rated breakingcapacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
10/10 |
15/15 |
15/15 |
|||||
500 V |
50/50 |
50/50 |
50/50 |
||||||||
440 V |
65/65 |
65/65 |
65/65 |
||||||||
400 V |
70/70 |
70/70 |
70/70 |
||||||||
230 V |
100/100 |
100/100 |
100/100 |
||||||||
Dimensions WxHxD |
[mm] |
140/185x257x103 |
140/185x257x103 |
210/280x275x103 |
|||||||
Type |
NF400-REW |
NF630-REW |
NF800-REW |
||||||||
R series |
Rated current I n max. [A] |
400* |
630* |
800* |
|||||||
Rated insulation voltage U i [V] |
AC |
690 |
690 |
690 |
|||||||
Number of poles |
3 |
3 |
3 |
||||||||
Rated breakingcapacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
15/10 |
20/15 |
20/15 |
|||||
500 V |
70/35 |
70/35 |
70/35 |
||||||||
440 V |
125/63 |
125/63 |
125/63 |
||||||||
400 V |
125/63 |
125/63 |
125/63 |
||||||||
230 V |
150/75 |
150/75 |
150/75 |
||||||||
Dimensions WxHxD |
[mm] |
140x257x103 |
140x257x103 |
210x275x103 |
|||||||
Type |
NF400-UEW |
NF800-UEW |
|||||||||
U series |
Rated current I n max. [A] |
400* |
800* |
||||||||
Rated insulation voltage U i [V] |
AC |
690 |
690 |
||||||||
Number of poles |
3/4 |
3/4 |
|||||||||
Rated breakingcapacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
35/35 |
35/35 |
||||||
500 V |
170/170 |
170/170 |
|||||||||
440 V |
200/200 |
200/200 |
|||||||||
400 V |
200/200 |
200/200 |
|||||||||
230 V |
200/200 |
200/200 |
|||||||||
Dimensions WxHxD |
[mm] |
140/280x297/322x200 |
210/280x322x200 |
||||||||
Type |
DSN400-SW |
DSN630-SW |
DSN800-SW |
DSN1000-SW |
DSN1250-SW |
DSN1600-SW |
|||||
Disconnectors |
Rated current I n max. [A] |
400 |
630 |
800 |
1000 |
1250 |
1600 |
||||
Rated insulation voltage U i [V] |
AC/DC |
690 |
690 |
690 |
660 |
660 |
660 |
||||
Rated voltage U e [V] |
AC (50/60 Hz)/DC |
690/250 |
690/250 |
690/250 |
660/250 |
660/250 |
660/250 |
||||
Number of poles |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
|||||
Max. switching current [A] (breaking) |
AC/DC |
3200/1600 |
5040/2520 |
6400/3200 |
8000/14000 |
10000/5000 |
12800/6400 |
||||
Dimensions WxHxD |
[mm] |
140/185x257x103 |
140/185x257x103 |
210/280x275x103 |
210/280x406x140 |
210/280x406x140 |
210/280x406x140 |
* adjustable
Wide assortment of products that is highly suitable for protection against overload, short-circuit conditions and electric shocks in low voltage circuits.
These are basic products for the protection of low voltage circuits. The WS-V series, Mitsubishi's latest series of Low Voltage Circuit Breakers, offers a number of different versions, including "F-style" small size breakers, with improved usability.
Type |
BV-DN |
NV125-CV |
NV250-CV |
||
---|---|---|---|---|---|
Rated current I n [A] |
|
10, 16, 20, 25, 32, 40 |
80, 100, 125 |
150, 175, 200, 225, 250 |
|
Number of poles |
|
2 (1+N) |
3 |
3 |
|
Rated voltage [V AC] |
|
230 |
100–440 |
100–440 |
|
Rated current sensitivity [mA] |
|
30 |
100/200/500 selectable |
100/200/500 selectable |
|
Max. operating time [s] |
|
0.04 |
0.45/1.0/2.0 selectable |
0.45/1.0/2.0 selectable |
|
Pulsating current sensitivity |
|
AC |
A (Harmonic Surge Ready) |
A (Harmonic Surge Ready) |
|
Rated breaking capacity [kA] |
230 V AC |
4.5 |
30 |
36 |
|
440 V AC |
— |
10 |
15 |
||
Number of operating cycles |
Without current |
20000 |
10000 |
8000 |
|
With current |
20000 (In 10, 16,20 A) 15000 (In 25 A) 10000 (In 32, 40 A) |
6000 |
4000 |
||
Dimensions [mm] |
a |
36 |
90 |
105 |
|
b |
88 |
130 |
165 |
||
c |
44 |
68 |
68 |
||
ca |
70 |
90 |
92 |
||
Mass [kg] |
0.19 |
1 |
1.7 |
||
Automatic tripping device |
Thermal-magnetic |
Thermal-magnetic |
Thermal-magnetic |
||
Based on standard |
IEC61009-1 |
IEC60947-2 |
IEC60947-2 |
||
Breaker type |
MCB |
MCCB |
MCCB |
||
CE marking |
Self-declaration |
Self-declaration |
TÜV approval |
Type |
2P (1P+N) |
3P |
---|---|---|
RCBO (Residual current circuit breakers with overcurrent protection) |
||
BV-DN 1PN 10A 30MA N |
248280 |
— |
BV-DN 1PN 16A 30MA N |
248283 |
— |
BV-DN 1PN 20A 30MA N |
248286 |
— |
BV-DN 1PN 25A 30MA N |
248289 |
— |
BV-DN 1PN 32A 30MA N |
248292 |
— |
BV-DN 1PN 10A 40MA N |
248295 |
— |
ELCB (Earth leakage circuit breakers) |
||
NV125-CV 3P 80A 2-440V 1.2.500MA JIEN CE |
— |
265624 |
NV125-CV 3P 100A 2-440V 1.2.500MA JIEN CE |
— |
265625 |
NV125-CV 3P 125A 2-440V 1.2.500MA JIEN CE |
— |
265626 |
NV250-CV 3P 150A 2-440V 1.2.500MA JIEN CE |
— |
265792 |
NV250-CV 3P 175A 2-440V 1.2.500MA JIEN CE |
— |
265793 |
NV250-CV 3P 200A 2-440V 1.2.500MA JIEN CE |
— |
265794 |
NV250-CV 3P 225A 2-440V 1.2.500MA JIEN CE |
— |
265795 |
NV250-CV 3P 250A 2-440V 1.2.500MA JIEN CE |
— |
265796 |
Miniature Circuit Breakers (MCBs) are compact electro-mechanical devices for up to 63A, for protection against overload and short-circuit conditions.
Mainly used for household applications and similar.
Standard: IEC60898-1
Breaking capacity:
4.5kA to 10kA 230/400VAC,
10kA 250VDC.
Product Specification:
Miniature circuit breakers (MCB)
Type |
BHW-T10 |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Miniature circuit breakers (MCB) |
|||||||||||
No. of poles P |
1 |
2 |
3 |
4 |
1 |
2 |
3 |
4 |
|||
Instantaneous tripping |
Type B |
Type C, D 1 |
|||||||||
Rated insulation voltage U i [V] |
660 |
660 |
|||||||||
Rated c urrent I n [A] at ambient temperature 30° C |
6, 10, 16, 20, 25, 32, 40, 50, 63 |
0.5, 1, 2, 3, 4, 5, 6, 10, 16, 20, 25, 32, 40, 50, 62 |
|||||||||
Rated short-circuit capacity [kA] |
IEC/EN 60898-1 (Icn) |
AC |
240 V |
10 |
10 |
||||||
240 V/ 415 V |
10 |
10 |
|||||||||
415 V |
— |
10 |
— |
10 |
|||||||
Energy limiting class 2 |
|
||||||||||
Number of operating cycles |
Without current |
|
|||||||||
With current |
|
||||||||||
Type of overcurrent release |
Thermal-magnetic |
||||||||||
Mounting |
IEC 35 mm rail |
||||||||||
Applicable wire size |
1 to 25 mm² |
||||||||||
Mass [kg] |
0.13 |
0.26 |
0.39 |
0.52 |
0.13 |
0.26 |
0.39 |
0.52 |
|||
Accessories (optional) 3 |
Auxiliary switch (AX) |
o |
|||||||||
Terminal connection |
Solderless |
||||||||||
Based on Standard |
IEC/EN 60898-1 |
||||||||||
CE marking |
o |
Type C: (5 In <, 10 In), Type D: (10 In <, 20 In)
Except for type D
Available soon
Standard: IEC61008
Type of residual current: Type AC
Product Specification:
Residual current breakers (RCCB) |
|||
---|---|---|---|
Type |
BVW-T |
||
No. of poles P |
2 (1+N) 1 |
4 (3+N) 1 |
|
Rated c urrent I n [A] at ambient temperature 30° C |
25, 40, 63 |
||
Rated voltage [V AC] |
240 |
415 |
|
Rated current sensitivity I g n [mA] |
30, 300 |
||
Max. operating time at I g n [s] |
0.04 |
||
Pulsating current sensitivity |
Type AC |
||
Rated making and breaking capacity I m [A] |
500 (In 25, 40 A), 630 (In 63 A) |
||
Rated conditional short-circuit current I nc [kA] |
5 |
||
Rated residual making and breaking capacity I g m [A] |
500 (In 25, 40 A), 630 (In 63 A) |
||
Rated conditional residual short-circuit current I g C [kA] |
6 |
||
Number of o perating cycles |
Without current |
4,000 2 |
|
With current |
2,000 |
||
Type of overcurrent release |
— |
||
Mounting |
IEC 35 mm rail |
||
Applicable wire size |
1 to 25 mm² |
||
Mass [kg] |
0.22 |
0.44 |
|
Terminal connection |
Solderless |
||
Based on standard |
IEC/EN 61008-1 |
||
CE marking |
o |
1 N pole is a switched neutral pole (without overcurrent release device).
Standard: IEC61009
Breaking capacity:
4.5kA 230VAC
Type of residual current: Type AC
Product Specification:
Type |
BV-DN |
NV125-CV |
NV250-CV |
||
---|---|---|---|---|---|
Rated current I n [A] |
|
10, 16, 20, 25, 32, 40 |
80, 100, 125 |
150, 175, 200, 225, 250 |
|
Number of poles |
|
2 (1+N) |
3 |
3 |
|
Rated voltage [V AC] |
|
230 |
100–440 |
100–440 |
|
Rated current sensitivity [mA] |
|
30 |
100/200/500 selectable |
100/200/500 selectable |
|
Max. operating time [s] |
|
0.04 |
0.45/1.0/2.0 selectable |
0.45/1.0/2.0 selectable |
|
Pulsating current sensitivity |
|
AC |
A (Harmonic Surge Ready) |
A (Harmonic Surge Ready) |
|
Rated breaking capacity [kA] |
230 V AC |
4.5 |
30 |
36 |
|
440 V AC |
— |
10 |
15 |
||
Number of operating cycles |
Without current |
20000 |
10000 |
8000 |
|
With current |
20000 (In 10, 16,20 A) 15000 (In 25 A) 10000 (In 32, 40 A) |
6000 |
4000 |
||
Dimensions [mm] |
a |
36 |
90 |
105 |
|
b |
88 |
130 |
165 |
||
c |
44 |
68 |
68 |
||
ca |
70 |
90 |
92 |
||
Mass [kg] |
0.19 |
1 |
1.7 |
||
Automatic tripping device |
Thermal-magnetic |
Thermal-magnetic |
Thermal-magnetic |
||
Based on standard |
IEC61009-1 |
IEC60947-2 |
IEC60947-2 |
||
Breaker type |
MCB |
MCCB |
MCCB |
||
CE marking |
Self-declaration |
Self-declaration |
TÜV approval |
Type |
2P (1P+N) |
3P |
---|---|---|
RCBO (Residual current circuit breakers with overcurrent protection) |
||
BV-DN 1PN 10A 30MA N |
248280 |
— |
BV-DN 1PN 16A 30MA N |
248283 |
— |
BV-DN 1PN 20A 30MA N |
248286 |
— |
BV-DN 1PN 25A 30MA N |
248289 |
— |
BV-DN 1PN 32A 30MA N |
248292 |
— |
BV-DN 1PN 10A 40MA N |
248295 |
— |
ELCB (Earth leakage circuit breakers) |
||
NV125-CV 3P 80A 2-440V 1.2.500MA JIEN CE |
— |
265624 |
NV125-CV 3P 100A 2-440V 1.2.500MA JIEN CE |
— |
265625 |
NV125-CV 3P 125A 2-440V 1.2.500MA JIEN CE |
— |
265626 |
NV250-CV 3P 150A 2-440V 1.2.500MA JIEN CE |
— |
265792 |
NV250-CV 3P 175A 2-440V 1.2.500MA JIEN CE |
— |
265793 |
NV250-CV 3P 200A 2-440V 1.2.500MA JIEN CE |
— |
265794 |
NV250-CV 3P 225A 2-440V 1.2.500MA JIEN CE |
— |
265795 |
NV250-CV 3P 250A 2-440V 1.2.500MA JIEN CE |
— |
265796 |
Miniature Circuit Breakers (MCBs) are compact electro-mechanical devices for up to 63A, for protection against overload and short-circuit conditions.
Mainly used for household applications and similar.
Standard: IEC60898-1
Breaking capacity:
4.5kA to 10kA 230/400VAC,
10kA 250VDC.
Type |
BHW-T10 |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Miniature circuit breakers (MCB) |
|||||||||||
No. of poles P |
1 |
2 |
3 |
4 |
1 |
2 |
3 |
4 |
|||
Instantaneous tripping |
Type B |
Type C, D 1 |
|||||||||
Rated insulation voltage U i [V] |
660 |
660 |
|||||||||
Rated c urrent I n [A] at ambient temperature 30° C |
6, 10, 16, 20, 25, 32, 40, 50, 63 |
0.5, 1, 2, 3, 4, 5, 6, 10, 16, 20, 25, 32, 40, 50, 62 |
|||||||||
Rated short-circuit capacity [kA] |
IEC/EN 60898-1 (Icn) |
AC |
240 V |
10 |
10 |
||||||
240 V/ 415 V |
10 |
10 |
|||||||||
415 V |
— |
10 |
— |
10 |
|||||||
Energy limiting class 2 |
|||||||||||
Number of operating cycles |
Without current |
||||||||||
With current |
|||||||||||
Type of overcurrent release |
Thermal-magnetic |
||||||||||
Mounting |
IEC 35 mm rail |
||||||||||
Applicable wire size |
1 to 25 mm² |
||||||||||
Mass [kg] |
0.13 |
0.26 |
0.39 |
0.52 |
0.13 |
0.26 |
0.39 |
0.52 |
|||
Accessories (optional) 3 |
Auxiliary switch (AX) |
o |
|||||||||
Terminal connection |
Solderless |
||||||||||
Based on Standard |
IEC/EN 60898-1 |
||||||||||
CE marking |
o |
Standard: IEC61008
Type of residual current: Type AC
Residual current breakers (RCCB) |
|||
---|---|---|---|
Type |
BVW-T |
||
No. of poles P |
2 (1+N) 1 |
4 (3+N) 1 |
|
Rated c urrent I n [A] at ambient temperature 30° C |
25, 40, 63 |
||
Rated voltage [V AC] |
240 |
415 |
|
Rated current sensitivity I g n [mA] |
30, 300 |
||
Max. operating time at I g n [s] |
0.04 |
||
Pulsating current sensitivity |
Type AC |
||
Rated making and breaking capacity I m [A] |
500 (In 25, 40 A), 630 (In 63 A) |
||
Rated conditional short-circuit current I nc [kA] |
5 |
||
Rated residual making and breaking capacity I g m [A] |
500 (In 25, 40 A), 630 (In 63 A) |
||
Rated conditional residual short-circuit current I g C [kA] |
6 |
||
Number of o perating cycles |
Without current |
4,000 2 |
|
With current |
2,000 |
||
Type of overcurrent release |
— |
||
Mounting |
IEC 35 mm rail |
||
Applicable wire size |
1 to 25 mm² |
||
Mass [kg] |
0.22 |
0.44 |
|
Terminal connection |
Solderless |
||
Based on standard |
IEC/EN 61008-1 |
||
CE marking |
o |
1 N pole is a switched neutral pole (without overcurrent release device).
Standard: IEC61009
Breaking capacity:
4.5kA 230VAC
Type of residual current: Type AC
Product Specification:
Type |
BV-DN |
NV125-CV |
NV250-CV |
||
---|---|---|---|---|---|
Rated current I n [A] |
|
10, 16, 20, 25, 32, 40 |
80, 100, 125 |
150, 175, 200, 225, 250 |
|
Number of poles |
|
2 (1+N) |
3 |
3 |
|
Rated voltage [V AC] |
|
230 |
100–440 |
100–440 |
|
Rated current sensitivity [mA] |
|
30 |
100/200/500 selectable |
100/200/500 selectable |
|
Max. operating time [s] |
|
0.04 |
0.45/1.0/2.0 selectable |
0.45/1.0/2.0 selectable |
|
Pulsating current sensitivity |
|
AC |
A (Harmonic Surge Ready) |
A (Harmonic Surge Ready) |
|
Rated breaking capacity [kA] |
230 V AC |
4.5 |
30 |
36 |
|
440 V AC |
— |
10 |
15 |
||
Number of operating cycles |
Without current |
20000 |
10000 |
8000 |
|
With current |
20000 (In 10, 16,20 A) 15000 (In 25 A) 10000 (In 32, 40 A) |
6000 |
4000 |
||
Dimensions [mm] |
a |
36 |
90 |
105 |
|
b |
88 |
130 |
165 |
||
c |
44 |
68 |
68 |
||
ca |
70 |
90 |
92 |
||
Mass [kg] |
0.19 |
1 |
1.7 |
||
Automatic tripping device |
Thermal-magnetic |
Thermal-magnetic |
Thermal-magnetic |
||
Based on standard |
IEC61009-1 |
IEC60947-2 |
IEC60947-2 |
||
Breaker type |
MCB |
MCCB |
MCCB |
||
CE marking |
Self-declaration |
Self-declaration |
TÜV approval |
Type |
2P (1P+N) |
3P |
---|---|---|
RCBO (Residual current circuit breakers with overcurrent protection) |
||
BV-DN 1PN 10A 30MA N |
248280 |
— |
BV-DN 1PN 16A 30MA N |
248283 |
— |
BV-DN 1PN 20A 30MA N |
248286 |
— |
BV-DN 1PN 25A 30MA N |
248289 |
— |
BV-DN 1PN 32A 30MA N |
248292 |
— |
BV-DN 1PN 10A 40MA N |
248295 |
— |
ELCB (Earth leakage circuit breakers) |
||
NV125-CV 3P 80A 2-440V 1.2.500MA JIEN CE |
— |
265624 |
NV125-CV 3P 100A 2-440V 1.2.500MA JIEN CE |
— |
265625 |
NV125-CV 3P 125A 2-440V 1.2.500MA JIEN CE |
— |
265626 |
NV250-CV 3P 150A 2-440V 1.2.500MA JIEN CE |
— |
265792 |
NV250-CV 3P 175A 2-440V 1.2.500MA JIEN CE |
— |
265793 |
NV250-CV 3P 200A 2-440V 1.2.500MA JIEN CE |
— |
265794 |
NV250-CV 3P 225A 2-440V 1.2.500MA JIEN CE |
— |
265795 |
NV250-CV 3P 250A 2-440V 1.2.500MA JIEN CE |
— |
265796 |
The best choice for overcurrent protection in North American countries.
These breakers comply with the American UL standard and the Canadian CSA standard, and are listed by UL. They are suitable for use with feeders and for branch circuit protection.
This kind of breaker complies to UL 489 and CSA C22.1No.5.
Product Specification:
Type |
NF125-UV |
NF250-UV |
NF400-UEW |
NF800-UEW |
|||||
---|---|---|---|---|---|---|---|---|---|
Rated data |
Rated current I n [A] at ambient temperature |
40 °C |
15, 20, 30, 40, 50, 60, 75, 100, 125 Fixed |
125, 150, 175, 200, 225, 250 Fixed |
200–400Adjustable |
500–1000Adjustable |
|||
Number of poles |
3/4 |
3/4 |
3/4 |
3/4 |
|||||
Rated insulation voltage U i [V] |
AC |
690 |
690 |
690 |
690 |
||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC/EN 60947-2 |
AC (50/60 Hz) |
690 V |
10/10 |
15/15 |
35/35 |
25/13 |
||
500 V |
200/200 |
200/200 |
170/170 |
65/33 |
|||||
440 V |
200/200 |
200/200 |
200/200 |
85/43 |
|||||
400 V |
200/200 |
200/200 |
200/200 |
85/43 |
|||||
230 V |
200/200 |
200/200 |
200/200 |
125/63 |
|||||
DC |
250 V |
— |
— |
B |
B |
||||
Utilization category |
A |
A |
5/0.25 |
20/0.3 |
|||||
Rated impulse withstand voltage U imp [kV] |
8 |
8 |
8 |
8 |
|||||
Pollution degree |
3 |
3 |
3 |
3 |
|||||
Reverse connection |
O |
O |
O |
O |
|||||
Suitable for isolation |
O |
O |
O |
O |
|||||
Mechanical data |
Dimensions [mm] |
a |
90/120 |
105/140 |
140/280 |
210/280 |
|||
b |
191 |
240 |
297/322 |
406 |
|||||
c |
68 |
68 |
200 |
140 |
|||||
ca |
92 |
92 |
252 |
190 |
|||||
Weight [kg] |
1.5/1.9 |
2.7/3.7 |
16.7/26.1 |
23.5/30.7 |
|||||
Cassette- type accessories |
Alarm switch |
(AL) |
O |
O |
O |
O |
|||
Auxiliary switch |
(AX) |
O |
O |
O |
O |
||||
Shunt trip |
(SHT) |
O |
O |
O |
O |
||||
Undervoltage trip |
Non-synchronous closing |
(UVT-N) |
O |
— |
O |
O |
|||
Synchronous closing |
(UVT-S) |
— |
O |
O |
O |
||||
Accessories connection |
With terminal block |
(SLT) |
O |
O |
O |
O |
|||
With internal terminal type |
O |
O |
O |
O |
|||||
Installation and connection |
Front |
Screw terminal (standard) |
O |
O |
O |
O |
|||
Solderless terminal |
O |
O |
O |
— |
|||||
Busbar terminal |
— |
— |
O /— |
— |
|||||
Rear |
(B) |
O |
O |
O |
O |
||||
Plug-in |
Rear |
(PM) |
—/ O |
— |
O |
O |
|||
Rear front IP 20 with auto trip |
(PM-IP) |
O /— |
O /— |
— |
O |
||||
Built-in accessories |
Pre-alarm-contact output a |
(PAL) |
— |
— |
— |
O |
|||
Overcurrent trip alarm a |
(OAL) |
— |
— |
— |
O |
||||
External accessories |
External operating handle |
Door mounting |
(V) |
O |
O |
O |
O |
||
Mounted on breaker |
(R) |
O |
O |
O |
— |
||||
Electrical operation device |
(MDS) |
O |
O |
O |
O |
||||
Handle lock device |
Handle lock for use with padlock |
(HL) |
O |
O |
O |
— |
|||
(HL-S) |
O |
O |
O |
O |
|||||
Lock cover |
(LC) |
O |
O |
O |
O |
||||
Terminal cover |
Large |
(TC-L) |
O |
O |
LR, GL, BV, AB |
LR, GL, AB |
|||
Small |
(TC-S) |
O |
O |
Electronic |
Electronic |
||||
For rear connection |
(BTC) |
O |
O |
Equipped |
Equipped |
||||
For plug-in |
(PTC) |
O |
O |
O |
O |
||||
Mechanical interlock |
(MI) |
O |
O |
O |
O |
||||
Insulating barrier |
Between phases (Standard) |
(BA-F) |
O |
O |
O |
O |
|||
Adapter for IEC 35 mm rail |
— |
— |
O /— |
O |
|||||
Others |
CE marking |
Self-declaration |
Self-declaration |
Self-declaration |
Self-declaration |
||||
CCC recognition |
— |
— |
Recognized |
Recognized |
|||||
Automatic tripping device |
Thermal-magnetic |
Thermal-magnetic |
Thermal-magnetic |
Thermal-magnetic |
|||||
Trip button |
Equipped |
Equipped |
Equipped |
Equipped |
This kind of breaker complies to UL 1053 and CSA C22.1No.144.
Upgrade your electrical equipment by using products suitable for your particular application.
If it is considered as proper when the standard MCCB/ELCB is not chosen to use in a special characteristic of the load, the special breaker is needed.
On creating an isolation switch (DSN) by omitting the overcurrent tripping device of a MCCB, it can be used as a switching device with high operating capacity.
Product Specification:
Type |
DSN32-SV |
DSN63-SV |
DSN125-SGV |
DSN160-SGV |
DSN250-SGV |
|||
---|---|---|---|---|---|---|---|---|
Disconnectors |
Rated current I n max. [A] |
32 |
63 |
125 |
160 |
250 |
||
Rated insulation voltage U i [V] |
AC/DC |
600 |
600 |
690 |
690 |
690 |
||
Rated voltage U e [V] |
AC (50/60 Hz)/DC |
500/250 |
500/250 |
690/300 |
690/300 |
690/300 |
||
Number of poles |
3 |
3/4 |
3/4 |
3/4 |
3/4 |
|||
Max. switching current [A] (breaking) |
AC/DC |
256/128 |
504/252 |
1000/500 |
1280/640 |
2000/1000 |
||
Dimensions WxHxD |
[mm] |
75x130x68 |
75/120x130x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
Type |
DSN400-SW |
DSN630-SW |
DSN800-SW |
DSN1000-SW |
DSN1250-SW |
DSN1600-SW |
|||
---|---|---|---|---|---|---|---|---|---|
Disconnectors |
Rated current I n max. [A] |
400 |
630 |
800 |
1000 |
1250 |
1600 |
||
Rated insulation voltage U i [V] |
AC/DC |
690 |
690 |
690 |
660 |
660 |
660 |
||
Rated voltage U e [V] |
AC (50/60 Hz)/DC |
690/250 |
690/250 |
690/250 |
660/250 |
660/250 |
660/250 |
||
Number of poles |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
|||
Max. switching current [A] (breaking) |
AC/DC |
3200/1600 |
5040/2520 |
6400/3200 |
8000/14000 |
10000/5000 |
12800/6400 |
||
Dimensions WxHxD |
[mm] |
140/185x257x103 |
140/185x257x103 |
210/280x275x103 |
210/280x406x140 |
210/280x406x140 |
210/280x406x140 |
Suitable for extending circuit breaker functions.
There are many different internal and external accessories. They can be used to make breakers safe and convenient.
These accessories are installed inside the breaker. AX indicates electrically the status of the breaker. AL indicates electrically the status of the breaker trip. SHT makes the breaker trip electrically by remote operation. UVT releases the breaker when the control voltage is dropped.
Product Specification:
Main MCCB conditions |
Alarm contacts |
---|---|
OFF or ON |
ALa 98 (open) ALc 95 (DC+) a ALb 96 (closed) |
Trip |
ALa 98 (closed) ALc 95 (DC+) a ALb 96 (open) |
Type of Micro-switch for |
Voltage (V AC) |
Resistive loads (A) |
Inductive load (A) |
Voltage (V DC) a |
Resistive loads (A) |
Inductive load (A) |
---|---|---|---|---|---|---|
AL/AX/ALAX-05–8 |
460 |
— |
— |
250 |
0.2 |
0.2 |
250 |
3 |
2 |
125 |
0.4 |
0.4 |
|
125 |
5 |
3 |
30 |
4 |
3 |
|
AL/AX/ALAX-10 |
460 |
5 |
2 |
250 |
0.3 |
0.3 |
250 |
10 |
10 |
125 |
0.6 |
0.6 |
|
125 |
10 |
10 |
30 |
10 |
6 |
MCCB type a |
Cut-off switch |
Voltage (V) b |
Input c |
Operating time(msec) d |
|
---|---|---|---|---|---|
AC (VA) |
DC (W) |
||||
NF32-SV NF63-SV NF63-HV |
Equipped |
AC 24–48 AC 100–240 AC 380–550 (50/60 Hz) DC 100–125 |
120 |
50 |
≤15 |
NF125-SGV/SEV NF125-HGV/HEV NF125-RGV/UGV NF160-SGV/SEV NF160-HGV/HEV NF250-SGV/SEV NF250-HGV/HEV NF250-RGV/UGV |
Equipped |
60 |
|||
NF400-SEW/HEW/REW/UEW NF630-SEW/HEW/REW NF800-CEW/SEW/HEW/REW/UEW |
Equipped |
AC 24–48/DC 24–48 AC 100–450/DC 100–200 AC 380–550 (50/60 Hz) |
100 V: 20 200 V: 50 330 V: 120450 V: 170 |
100 V: 10 200 V: 35 |
5–15 |
NF1000-SEW NF1250-SEW NF1600-SEW |
Equipped |
AC 100–120 AC 200–240 AC 380–450 (50/60Hz) DC 100 |
200 |
70 |
7–15 |
Main MCCB conditions |
Auxiliary contacts |
---|---|
OFF or Trip |
AXa 14 (open) AXc 11 (DC+) a AXb 12 (closed) |
ON |
AXa 14 (closed) AXc 11 (DC+) a AXb 12 (open) |
These accessories are mounted outside the breaker. An accessory operates electrically the breaker handle, or the external handle on the panel can be used for breaker operation.
Product Specification:
V-05SV |
V-05SVE |
V-1SV |
V-1SVE |
V-2SV |
V-2SVE |
V-2UV |
V-2UVE |
V-4S |
V-4SE |
V-8S |
V-8SE |
|
---|---|---|---|---|---|---|---|---|---|---|---|---|
Breaker type |
NF/DSN32-63 |
NF125-SV |
NF/DSN125-250-SGV/SEV |
NF/DSN125-250-UV |
NF/DSN400-630 |
NF/DSN800 |
||||||
Colour: handle/front |
black |
red/yellow |
black |
red/yellow |
black |
red/yellow |
black |
red/yellow |
black |
red/yellow |
black |
red/yellow |
Order information Art. no. |
267747 |
267749 |
267751 |
267753 |
267755 |
267756 |
267757 |
267758 |
225420 |
225421 |
225424 |
225425 |
V-AD3S |
V-AD5S |
V-AD3L |
V-AD5L |
|
---|---|---|---|---|
Breaker type |
NF/DSN32-250 |
NF/DSN400-800 |
||
Approx. length (mm) |
300 |
500 |
300 |
500 |
Order information Art. no. |
225426 |
235194 |
225427 |
235235 |
For the WS-V series electronic type breakers, 125 to 250A frame, this device can used to perform release tests, as well as for monitoring and set-up of operating characteristics.