Integration of Low Voltage Circuit Breakers and Thermal Overload Relay functions.
This device is capable of protecting motor branch circuits from overload, phase-loss, and short-circuit.
It offers even more secure wiring and motor protection.
Space-saving design has lead to down-sizing of the control panel.
The rated short-circuit breaking capacity satisfies 10KA at a voltage of 200-240VAC.
Type name |
MMP–T32 |
MMP–T32LF |
||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Standard |
JIS C8201-2-1 Ann.1, JIS 8201-4-1, EN60947-2, EN60947-4-1, IEC60947-2, IEC60947-4-1, GB14048.2 UL60947-4-1A, CSAC22.2NO.60947-4-1 |
EN60947-2, EN60947-4-1, IEC60947-2, IEC60947-4-1, GB14048.2 |
||||||||||||
Number of poles |
3 |
|||||||||||||
Handle shape |
Tumbler handle |
|||||||||||||
Rated current in [A] |
0.1 to 32 |
|||||||||||||
Rated operational voltage Ue [V] |
200 to 690 |
|||||||||||||
Rated frequency [Hz] |
50/60 |
|||||||||||||
Rated insulation voltage Ui [V] |
690 |
|||||||||||||
Rated impulse withstand voltage Uimp [kV] |
6 |
|||||||||||||
Rated short-circuit breaking capacity [kA] JIS C8201-2-1Ann.1 IEC60947-2 |
Rated current Ie [A] |
200/240 V |
400/415 V |
440/460 V |
200/240 V |
400/415 V |
440/460 V |
|||||||
Heater designation |
Current setting range |
lcu |
lcs |
lcu |
lcs |
lcu |
lcs |
lcu |
lcs |
lcu |
lcs |
lcu |
lcs |
|
0.16 |
0.1–0.16 |
100 |
100 |
100 |
100 |
100 |
100 |
|||||||
0.25 |
0.16–0.25 |
100 |
100 |
100 |
100 |
100 |
100 |
|||||||
0.4 |
0.25–0.4 |
100 |
100 |
100 |
100 |
100 |
100 |
|||||||
0.63 |
0.4–0.63 |
100 |
100 |
100 |
100 |
100 |
100 |
|||||||
1 |
0.63–1 |
100 |
100 |
100 |
100 |
100 |
100 |
|||||||
1.6 |
1–1.6 |
100 |
100 |
100 |
100 |
100 |
100 |
|||||||
2.5 |
1.6–2.5 |
100 |
100 |
100 |
100 |
100 |
100 |
|||||||
4 |
2.5–4 |
100 |
100 |
100 |
100 |
100 |
100 |
|||||||
6.3 |
4–6.3 |
100 |
100 |
100 |
100 |
100 |
50 |
50 |
||||||
8 |
5.5–8 |
100 |
100 |
50 |
38 |
100 |
100 |
15 |
15 |
|||||
10 |
7–10 |
100 |
100 |
50 |
38 |
100 |
100 |
15 |
15 |
|||||
13 |
9–13 |
100 |
100 |
50 |
38 |
100 |
15 |
7.5 |
8 |
4 |
||||
18 |
12–18 |
100 |
50 |
38 |
35 |
27 |
100 |
15 |
7.5 |
8 |
4 |
|||
25 |
18–25 |
100 |
50 |
38 |
35 |
27 |
50 |
15 |
6 |
6 |
3 |
|||
32 |
24–32 |
100 |
50 |
38 |
35 |
27 |
50 |
10 |
5 |
6 |
3 |
|||
Selectivity category |
JIS C8201-2-1 Ann.1 IEC60947-2 |
Cat.A |
||||||||||||
Utilization category |
JIS C8201-4-1 IEC60947-4-1 |
AC-3 |
||||||||||||
Trip class (JIS C8201-4-1, IEC60947-4-1) |
10 |
|||||||||||||
Instantaneous release current |
13 x Maximum Ie |
|||||||||||||
Durability |
Mechanical [times] |
100,000 |
||||||||||||
Electrical [times] |
100,000 |
|||||||||||||
Phase loss sensitive |
Yes |
|||||||||||||
Trip display |
Yes |
|||||||||||||
Test trip function |
Yes |
|||||||||||||
Auxiliary contact unit |
UT-MAX (1a or 1b) AC-12: 125 V/5 A, 250 V/3 A |
|||||||||||||
Alarm contact unit |
UT-MAL (1a or 1b) DC-12: 125 V/0.4 A, 250 V/0.2 A |
|||||||||||||
Short-circuit indicator unit |
UT-TU |
|||||||||||||
Weight [g] |
330 |
Breaking capacity at 415 V |
Current setting range |
Model |
Code |
---|---|---|---|
100 KA |
0.1–0.16 A |
MMP-T32LF-0.16A |
288426 |
100 KA |
0.16–0.25 A |
MMP-T32LF-0.25A |
288427 |
100 KA |
0.25–0.4 A |
MMP-T32LF-0.4A |
288428 |
100 KA |
0.4–0.63 A |
MMP-T32LF-0.63A |
288429 |
100 KA |
0.6–1 A |
MMP-T32LF-1.0A |
288430 |
100 KA |
1–1.6 A |
MMP-T32LF-1.6A |
288431 |
100 KA |
1.6–2.5 A |
MMP-T32LF-2.5A |
288432 |
100 KA |
2.5–4 A |
MMP-T32LF-4.0A |
288433 |
100 KA |
4–6.3 A |
MMP-T32LF-6.3A |
288434 |
100 KA |
5.5–8 A |
MMP-T32LF-8A |
288435 |
100 KA |
7–10 A |
MMP-T32LF-10A |
288436 |
15 KA |
9–13 A |
MMP-T32LF-13A |
288437 |
15 KA |
12–18 A |
MMP-T32LF-18A |
288438 |
15 KA |
18–25 A |
MMP-T32LF-25A |
488439 |
10 KA |
24–32 A |
MMP-T32LF-32A |
288440 |
100 KA |
9–13 A |
MMP-T32-13A |
288441 |
50 KA |
12–18 A |
MMP-T32-18A |
288442 |
50 KA |
18–25 A |
MMP-T32-25A |
288443 |
50 KA |
24–32 A |
MMP-T32-32A |
288444 |
There are many optional units for motor circuit breakers.